Having now maintained our own interior, Integrated Wood & Oil Heating System since 1975 and more recently coupling Outdoor Wood Boilers to our Weil-McLain FHW Heating Systems, we are motivated to pass on some of our observations.
Note hyperlinks within document.
Disclaimer: We are exclusive Weil-McLain Heating Designers & Installers here in NH only (thus far). We do not nor have not specified, sold or initially installed any interior or outdoor “Solid Fuel” (Wood, Pellets, Coal, etc.) Boilers. Our participation has been to occasionally help out a customer integrate these products with our Weil-McLain Hydronic Heating Systems per our personal experience. Included has been converting Steam Boiler Systems to FHW and conjoining these systems.
The recent popularity of Outdoor Wood Boilers in particular has prompted many inquiries and discussions on our part. They seem however to neglect the interior-located solid fuel boiler in the scope of options. Each of these have distinctive attributes that both complement and complicate their integration and operational effectiveness.
Inside or outside? That is the (first) question and may likely be answered by The Regulators (Zoning, Fire and Insurers). Specifically to wood/coal boilers:
- The Local Zoning Code will define permitted use and location parameters. (Outdoor Boilers are particularly vulnerable to NIMBY (Not In My Back Yard) and more specifically regulated.)
- The Fire Codes usually reference both, but are tough on Interior Boilers.
- Insurers (risk takers) then determine how much it is going to cost you to save money. Again, interior boilers take the major hit, especially if it is the primary energy source.
Note: The delineation is between Gas/Oil-fired Power Burner Heating Systems and Solid-Fuel Fire (Coal/Wood, etc.) Systems. Insurers will usually bend for Automatic Stoker-fed Coal and Automatic Wood Pellet Systems with a two-week continuous-feed fuel storage supply. Check your local codes and insurers, however.
At the risk of oversimplification and generalization we offer the following:
Type
Flue
Loop Length
Loop Losses
Standby Losses
Effiency (Overall)
Interior
Req'd
Short
Low
Low
Moderate to High
Outdoor
N/A
Long
High
High
Low to Moderate
Explanations:
Flue:
Any Interior Wood/Coal Heater REQUIRES A DEDICATED CHIMNEY FLUE! Flue quality must also be considered to support a continuous fuel fire. A “sometimes option” is to convert the primary powered burner (gas/oil) appliance to a “direct vent” device vs. the additional flue construction cost. Check it out.
The Outdoor Wood/Coal Boiler has its own integral exhaust stack. However it is not unusual to see vertical stack added, sometimes up to 20 ft. to improve draft or smoke dissipation conditions.
Loop Length:
An Interior Wood/Coal Boiler can be readily be coupled to a FHW System, given flue location options. Interior Boilers are typically like-pressurized and therefore operationally compatible.
An Outdoor Wood/Coal Boiler is typically “Zero Pressure” to simplify construction, ease of operation and complexity. This comes at a price with a continuously-powered, “high head” (flow resistance) system loop to the FHW System using a tough circulator. An in-line Heat Exchanger is required to mate the pair. Significant heat losses occur as well.
Loop Losses:
Interior Wood/Coal Boiler Loop Losses are typically dissipated to the ambient surrounding area and usually indirectly contribute to the heating of the structure.
Outdoor Wood/Coal Boiler Interior Loop Losses are as prior, but Exterior Losses are very significant! (We have a system with over 400 feet of high quality, insulated two-pipe, buried down several feet. You can readily observe the reduced/absence-of-snow line path.) You must further isolate the “Zero-Pressure” Outdoor water from the interior “Pressurized” water using a “Plate-To-Plate” Heat Exchanger System with controls & circulators. This system contributes some heat to the ambient area, however.
Standby Losses: (Defined as energy losses between heat demand cycles.)
All Interior Boilers dissipate energy between cycles to the ambient and incur flue losses (heat up the chimney). The chassis and piping energy is generally accepted to be contributing to the heating environment positively excepting during the non-heating season.
All Outdoor Boilers lose significant energy both from their chassis (never any snow on them) and their exterior service loop if circulation is not inhibited with demand. All this is lost energy by definition.
Efficiency (Overall):
Albeit being an empirical determination, the relative efficiencies of interior vs. outdoor boiler systems will be effectively higher due to their placements (in heat value areas) and reduced loop and standby losses. Thus the terminologies assigned and relationship to each other.
Note: We are not addressing the Heat Generation Efficiencies of any boiler products in our discussion, these varying by configuration(s), but their overall performance by type. Open the NH Fuel Price Calculator (Excel Doc) and the ADVANCE CALCULATOR page for more definitive detail.
Operational Observations:
Further observations of field operation leads us to believe that many outdoor boiler users fire them virtually continuously, incurring very poor fuel utilization, during low heat demand periods. Perhaps there is a continuing need for DHW (Domestic Hot Water) Generation without a storage means provided, or an unwillingness to build a new fire.
We have evidenced outdoor wood systems consuming 11 cords of wood that in our humble opinion should be consuming no more than 5 cords with an interior boiler, 45% of the outdoor unit. Granted this is a very heuristic and unqualified determination, but yet an indicative one.
Whatever the case, if one presumes to maximize his fuel utilization the household must adapt to the characteristics of the solid fuel fired system. “Showers-On-Demand” will likely require a generously sized Indirect Water Heater (Super-insulated DHW Storage Tank) to accommodate this lifestyle. Otherwise an incremental or even seasonal fallback to the gas/oil-fired system may be necessitated, and desirable.
There is a tendency of auxiliary wood/coal users to “over-engineer” their systems. A prolific use of circulators, relays and controls result. We would respectfully suggest that exploring the use of Delta-T Circulator Technology would benefit energy management. Further, employing Zone Valves with these may permit some emergency (no power) gravity heating, particularly on interior boiler systems.
Conclusions:
- Outdoor Wood Boilers appeal to users who have larger fuel demands, a low-cost supply of particularly cordwood, time and resources available to process it. (As we say: “Wood warms you twice!”) Poorer total fuel efficiency is a definite factor in their consideration.
- Outdoor Wood Boilers in particular require continuous electrical energy for combustion and distribution. No Power — No Heat! (Or it’s a generator, too.)
- Interior Coal/Wood Boilers are operationally more desirable, but regulatory influences must be qualified and satisfied.
- Installed Costs of any dual-fuel system are substantial. To minimize this and achieve predictable performance, use of a qualified technical resource is recommended. Utilize a “system guy” and not just a “tech-sketch” provided by the boiler salesman.
- Not maintaining ideal and consistent heated water delivery in any system takes its toll on equipment, in particular circulators, through very long duty cycling.
Our Personal System and Performance Data:
Referencing our Blog on our personal system, we offer the following:
- Operating as an oil-only system between 1971-1975
- Annual Fuel Oil Consumption: 475 Gallons x 140KBTU = 66.5MBTU/Yr @ 85% Efficiency = 56.5MBTU/Yr. Net Usable Energy
- Operated as a wood-only system between 1986-1995 (9 yrs.)
- Annual Wood Fuel Consumption: 4-1/2 Cords average x 20MBTU/Cord = 90MBTU/Yr. @ 60% Efficiency = 54MBTU/Yr. Net Usable Energy
- Operating as a dual fuel system otherwise between 1975-1985 and 1995 to date. We have been using only a modest amount of wood recently due to time constraints.
This Heating Season to Date: 200+ Gallons of Fuel and 1+ Cord of Wood + combustible paper & other waste, as available. (Admittedly approximations.)
10 Room Single Family Home, Built 1970, Heated Area: 2,016 Sq Ft
3-1/2 Zone, Programmed T-Stats, Coupled FHW Oil and Wood Boilers. DHW Immersion Coil on Oil Boiler. Planned Upgrade: Large Indirect Water Heater for DHW to permit less low/no heating season boiler cycling.
Degree Days: 7,500 Average (SW NH)
Comments:
Dual-fuel and in particular interconnected FHW boiler systems offer a good heating option, given they be properly configured and operated. We have a long ways to go to inform and guide customers in their application and execution. It is our hope that this document is of some help toward this end.